Description
Power supply module X80 – 100..240 V AC
range of product |
Modicon X80
|
|
---|---|---|
product or component type |
Power supply module
|
|
backplane compatibility |
All backplane
|
|
advanced diagnostics available via network |
Temperature sensing
Redundancy test Uptime duration Redundancy information Remaining lifetime |
|
primary voltage |
100…240 V
|
|
supply circuit type |
AC
|
|
secondary power |
18 W 3.3 V DC 32…140 °F (0…60 °C) I/O module logic power supply
40 W 24 V DC 32…140 °F (0…60 °C) I/O module power supply and processor if 3.3 V not loaded |
primary voltage limit |
85…264 V
|
|
---|---|---|
network frequency |
50/60 Hz
|
|
network frequency limits |
47…63 Hz
|
|
apparent power |
0.07 kVA
|
|
input current |
0.52 A 240 V
1.04 A 115 V |
|
inrush current |
30 A 120 V
60 A 240 V |
|
I²t on activation |
1 A².s 115 V
4 A².s 230 V |
|
It on activation |
0.1 A.s 115 V
0.15 A.s 230 V |
|
protection type |
Internal fuse not accessible for primary circuit
Overload protection for secondary circuit Overvoltage protection for secondary circuit Short-circuit protection for secondary circuit |
|
current at secondary voltage |
5.5 A 3.3 V DC I/O module logic power supply
1.67 A 24 V DC I/O module power supply and processor |
|
maximum power dissipation in W |
8.5 W
|
|
status LED |
1 LED (green)presence of voltages (OK)
1 LED (green)redundancy OK 1 LED (green)power supply status |
|
control type |
RESET push-button cold restart
|
|
electrical connection |
1 connector 2 alarm relay
1 connector 5 line supply, protective earth |
|
insulation resistance |
>= 100 MOhm primary/ground
>= 100 MOhm primary/secondary |
|
Net Weight |
1.12 lb(US) (0.51 kg)
|
immunity to microbreaks |
1 ms
|
|
---|---|---|
dielectric strength |
1500 V primary/secondary I/O module logic power supply
1500 V primary/secondary I/O module power supply and processor 2300 V primary/secondary sensor power supply 1500 V primary/ground 500 V 24 V sensor output/ground |
|
vibration resistance |
3 gn
|
|
shock resistance |
30 gn
|
|
IP degree of protection |
IP20
|
|
directives |
2014/35/EU – low voltage directive
2014/30/EU – electromagnetic compatibility |
|
environmental characteristic |
3C3 EN/IEC 60721-3-3
3C4 EN/IEC 60721-3-3 |
|
ambient air temperature for storage |
-40…185 °F (-40…85 °C)
|
|
ambient air temperature for operation |
32…140 °F (0…60 °C)
|
|
relative humidity |
5…95 % 131 °F (55 °C) without condensation
|
|
protective treatment |
TC
Conformal coating Humiseal 1A33 |
|
operating altitude |
0…2000 m
2000…5000 m with derating factor |