Description
Discrete output module X80 – 16 outputs – solid state – 24 V DC negative
range of product |
Modicon X80
|
|
---|---|---|
product or component type |
Discrete output module
|
|
discrete output number |
16
|
|
discrete output type |
Solid state
|
|
discrete output logic |
Negative
|
|
discrete output voltage |
24 V 19…30 V DC
|
|
discrete output current |
0.5 A
|
current per channel |
0.625 A
|
|
---|---|---|
maximum current per module |
10 A
|
|
maximum leakage current |
0.5 mA at state 0
|
|
maximum voltage drop |
<1.2 V at state 1
|
|
insulation resistance |
> 10 MOhm 500 V DC
|
|
power dissipation in W |
2.26 W
|
|
response time on output |
1.2 ms
|
|
paralleling of outputs |
Yes : 3 maximum
|
|
typical current consumption |
79 mA at 3.3 V DC
|
|
MTBF reliability |
403804 H
|
|
protection type |
reverse polarity protection
External short-circuit protection overload protection overvoltage protection |
|
output overload protection |
With electronic circuit breaker 1.5 In < Id < 2 In
With current limiter |
|
output overvoltage protection |
With transil diode
|
|
output short-circuit protection |
With 2 A external fuse
|
|
reverse polarity protection |
Reverse mounted diode
|
|
voltage detection threshold |
< 14 V DC preactuator fault
> 18 V DC preactuator at state 0 |
|
maximum tungsten load |
6 W
|
|
switching frequency |
0.5/LI² Hz
|
|
load impedance ohmic |
>= 48 Ohm
|
|
status LED |
1 LED (green)module operating (RUN)
1 LED per channel (green)channel diagnostic 1 LED (red)module error (ERR) 1 LED (red)module I/O |
|
net weight |
0.12 kg
|
IP degree of protection |
IP20
|
|
---|---|---|
directives |
2014/35/EU – low voltage directive
2014/30/EU – electromagnetic compatibility |
|
dielectric strength |
1500 V AC at 50/60 Hz 1 minute, output/ground
1500 V AC at 50/60 Hz 1 minute, output/internal logic |
|
vibration resistance |
3 gn
|
|
shock resistance |
30 gn
|
|
ambient air temperature for storage |
-40…85 °C
|
|
ambient air temperature for operation |
0…60 °C
|
|
relative humidity |
5…95 % at 55 °C without condensation
|
|
operating altitude |
0…2000 m
2000…5000 m with derating factor |