Sale!

140ACO02000

Original price was: $ 1,885.00.Current price is: $ 1,450.00.

Analog Output Module Modicon Quantum – 4 O – 4..20 mA – 12 Bits Bipolar Current

In stock

Category: Tag:

Description

Analog Output Module Modicon Quantum – 4 O – 4..20 mA – 12 Bits Bipolar Current

Main
range of product
Modicon Quantum automation platform
product or component type
Analogue output module
Complementary
analogue output number
4
addressing requirement
4 output words
loop voltage
12…30 V DC
voltage drop
30 V 20 mA
analogue output range
4…20 mA 0…4096 counts, 12 bits bipolar current
absolute accuracy error
+/- 0.20 % of full scale at 77 °F (25 °C)
linearity
+/- 1 LSB
accuracy drift according to temperature
+/- 0.004 % of full scale/°C
+/- 0.007 % of full scale/°C maximum
isolation between channels
500 V 47…63 Hz AC
750 V for 1 minute DC
update time
3 ms
setting time
900 µs to +/- 0.1 % of the final value
fault type
Open circuit 4…20 mA
bus current requirement
480 mA
power dissipation in W
<= 5.3 W
external power requirement
12…30 V
marking
CE
local signalling
4 LEDs green channel is turned on
4 LEDs red channel fault
1 LED green bus communication is present (Active)
1 LED red external fault
module format
Standard
product weight
0.66 lb(US) (0.3 kg)
Environment
product certifications
CUL
FM Class 1 Division 2
standards
CSA C22.2 No 142
UL 508
resistance to electromagnetic fields
9.14 V/yd (10 V/m) 80…2000 MHz conforming to IEC 801-3
ambient air temperature for operation
32…140 °F (0…60 °C)
ambient air temperature for storage
-40…185 °F (-40…85 °C)
relative humidity
95 % without condensation
operating altitude
<= 16404.2 ft (5000 m)