Description
Analog Output Module Modicon Quantum – 8 O Multirange
range of product |
Modicon Quantum automation platform
|
|
---|---|---|
product or component type |
Analogue output module
|
analogue output number |
8
|
|
---|---|---|
addressing requirement |
8 output words
|
|
loop voltage |
6…30 V DC
|
|
voltage drop |
30 V 25 mA
|
|
analogue output range |
0…20 mA 0…20000 counts
0…25 mA 0…25000 counts 4…20 mA 0…16000 counts 4…20 mA 0…4095 counts |
|
absolute accuracy error |
+/- 0.2 % of full scale at 77 °F (25 °C)
|
|
linearity |
+/- 12 µA 4…20 mA 0…4095 counts
+/- 4 µA 0…20 mA 0…20000 counts +/- 4 µA 0…25 mA 0…25000 counts +/- 4 µA 4…20 mA 0…16000 counts |
|
accuracy drift according to temperature |
0.004 % of full scale/°C typical
0.007 % of full scale/°C maximum |
|
isolation between channels and bus |
1780 V for 1 minute AC
|
|
update time |
5 ms
|
|
setting time |
1.6 ms to 5% of the final value
3.2 ms to +/-0.1% of the final value |
|
fault type |
Open circuit 4…20 mA
|
|
bus current requirement |
550 mA
|
|
power dissipation in W |
5 W
|
|
external power requirement |
6…30 V
|
|
marking |
CE
|
|
local signalling |
1 LED green bus communication is present (Active)
1 LED red external fault 8 LEDs green channel is turned on 8 LEDs red channel fault |
|
module format |
Standard
|
|
product weight |
0.66 lb(US) (0.3 kg)
|
product certifications |
CUL
FM Class 1 Division 2 |
|
---|---|---|
standards |
CSA C22.2 No 142
UL 508 |
|
resistance to electromagnetic fields |
9.14 V/yd (10 V/m) 80…2000 MHz conforming to IEC 801-3
|
|
ambient air temperature for operation |
32…140 °F (0…60 °C)
|
|
ambient air temperature for storage |
-40…185 °F (-40…85 °C)
|
|
relative humidity |
95 % without condensation
|
|
operating altitude |
<= 16404.2 ft (5000 m)
|