Description
Analog Input Module Modicon Quantum – 8 I Ni / Pt 100, 200, 500, 1000
range of product |
Modicon Quantum automation platform
|
|
---|---|---|
product or component type |
Analogue input module
|
analogue input number |
8
|
|
---|---|---|
input type |
Differential
|
|
addressing requirement |
9 input words
|
|
analogue input type |
Temperature probe – 100…450 °C Pt 100, Pt 200, Pt 500, Pt 1000
Temperature probe – 200…850 °C Pt 100, Pt 200, Pt 500, Pt 1000 Temperature probe – 60…180 °C Ni 100, Ni 200, Ni 500, Ni 1000 Temperature probe 0.5 mA Ni 100, Ni 200, Ni 500, Ni 1000 Temperature probe 2.5 mA Pt 100, Pt 200, Ni 100, Ni 200 |
|
analogue input resolution |
13 bits
|
|
input impedance |
>= 10 MOhm
|
|
absolute accuracy error |
0.1 °C
|
|
linearity error |
+/- 0.01 % full scale
+/- 0.5 °C |
|
accuracy drift according to temperature |
+/- 0.5 °C at 77 °F (25 °C)
+/- 0.9 °C at 32…140 °F (0…60 °C) |
|
isolation between channels and bus |
2500 V DC for 60 s
1780 V AC 47…63 Hz for 60 s |
|
isolation between channels |
300 Vrms AC
|
|
update time |
1200 ms 3 wires
640 ms 2 wires/4 wires |
|
fault type |
Broken wire
Overtacking scale |
|
marking |
CE
|
|
local signalling |
1 LED green bus communication is present (Active)
1 LED red external fault 8 LEDs green channel is turned on 8 LEDs red channel fault |
|
bus current requirement |
200 mA
|
|
power dissipation in W |
1 W
|
|
module format |
Standard
|
|
product weight |
0.66 lb(US) (0.3 kg)
|
standards |
CSA C22.2 No 142
UL 508 |
|
---|---|---|
product certifications |
CUL
FM Class 1 Division 2 |
|
resistance to electrostatic discharge |
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2 |
|
resistance to electromagnetic fields |
9.14 V/yd (10 V/m) 80…1000 MHz conforming to IEC 801-3
|
|
ambient air temperature for operation |
32…140 °F (0…60 °C)
|
|
ambient air temperature for storage |
-40…185 °F (-40…85 °C)
|
|
relative humidity |
95 % without condensation
|
|
operating altitude |
<= 16404.2 ft (5000 m)
|