Description
Unity Processor Modicon Quantum – 1056Kb – 66MHz
range of product |
Modicon Quantum automation platform
|
|
---|---|---|
product or component type |
Unity processor
|
clock frequency |
66 MHz
|
|
---|---|---|
number of slots |
10
4 16 2 6 |
|
number of racks |
2 – local rack(s)
|
|
number of distributed I/O station |
63 station(s) – 1 rack(s) – 3 Modbus Plus network(s)
|
|
number of remote I/O station |
31 – 2 S908 remote I/O rack(s)
0 – 0 ethernet remote I/O rack(s) |
|
discrete I/O number |
8000 inputs, 8000 outputs – distributed – per network Modbus Plus
Unlimited (26 slots max) – local 31744 inputs, 31744 outputs – remote |
|
analogue I/O number |
Unlimited (26 slots max) – local
1984 inputs,1984 outputs – S908 remote I/O 500 inputs, 500 outputs – distributed – per network Modbus Plus |
|
application specific I/O |
Counter
Serial link High-speed interrupt inputs Accurate time stamping |
|
number of optional modules |
6 ( Ethernet, Modbus, Modbus Plus, Profibus DP, Sy/Max)
|
|
maximum number of connections |
2 ( AS-Interface) – distributed
2 ( Modbus) – RS232/485 Modbus/ASCII 4 ( AS-Interface) – remote 6 ( Ethernet TCP/IP) – local 6 ( Modbus Plus) – local 6 ( Profibus DP) – local |
|
integrated connection type |
1 Modbus Plus with
2 Modbus with |
|
checks |
Process control
|
|
memory description |
Internal RAM 1056 kB
|
|
switch function |
Key switch memory start/stop memory protection
Slide switch communication port : ASCII/RTU/Memory |
|
application structure |
1 cyclic/periodic master task –
1 periodic fast task – 16 timer interrupt tasks – 64 I/O interrupt tasks – 64 interrupt tasks – No auxiliary task – |
|
execution time per instruction |
0.1…0.27 µs floating points
0.1…0.27 µs on fixed-point arithmetic 0.12…0.585 µs Boolean 0.12…0.585 µs on word |
|
number of instructions per ms |
1.86 Kinst/ms if 100 % Boolean
2.49 Kinst/ms if 65 % Boolean and 35 % numerical |
|
system overhead |
1 ms – master task
0.2 ms – fast task |
|
bus current requirement |
1800 mA
|
|
local signalling |
1 LED green communications are active on the Modbus Plus port (Modbus Plus)
1 LED green communications are active on the Modbus port (Modbus) 1 LED green CPU has been started and is solving logic (RUN) 1 LED green CPU has passed the power-up diagnostic tests (READY) 1 LED orange write-protected memory (memory port) 1 LED red battery needs replacing or is not present (BAT LOW) 1 LED red communications error on the Modbus Plus port (ERROR A) |
|
electrical connection |
1 female connector, connector type: SUB-D 9 for connecting to the Modbus Plus network
2 female connectors, connector type: SUB-D 9 for connecting to the Modbus bus |
product certifications |
UL
CSA CE |
|
---|---|---|
standards |
HazLoc
|
Category |
18150 – QUANTUM CONTROLLERS,HSBY,COMM.
|
|
---|---|---|
Discount Schedule |
PC21
|
|
GTIN |
00785901421078
|
|
Nbr. of units in pkg. |
1
|
|
Package weight(Lbs) |
1.3500000000000001
|
|
Returnability |
N
|
|
Country of origin |
FR
|