Description
Analog Input Module Modicon Quantum – 8 I Thermocouple
range of product |
Modicon Quantum automation platform
|
|
---|---|---|
product or component type |
Analogue input module
|
|
type of filter |
Notch filter – 3 dB at 50/60 Hz
Single pole low pass – 3 dB at 20 Hz |
analogue input number |
8
|
|
---|---|---|
addressing requirement |
10 input words
|
|
analogue input type |
Thermocouple – 210…760 °C thermocouple J
Thermocouple – 270…1000 °C thermocouple E Thermocouple – 270…1370 °C thermocouple K Thermocouple – 270…400 °C thermocouple T Thermocouple – 50…1665 °C thermocouple R Thermocouple – 50…1665 °C thermocouple S |
|
analogue input resolution |
16 bits
|
|
input impedance |
> 1 MOhm
|
|
absolute accuracy error |
+/- 2 °C plus + 0.1 % of reading thermocouple J
+/- 2 °C plus + 0.1 % of reading thermocouple K +/- 2 °C plus + 0.1 % of reading thermocouple T +/- 4 °C plus + 0.1 % of reading thermocouple R +/- 4 °C plus + 0.1 % of reading thermocouple S +/- 2 °C plus + 0.1 % of reading thermocouple E |
|
linearity error |
1 °C, 0.1 °C, 1 F, 0.1 F – 210…760 °C
1 °C, 0.1 °C, 1 F, 0.1 F – 270…1000 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 270…1370 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 270…400 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 50…1665 °C |
|
accuracy drift according to temperature |
0.15 µV/°C + 0.0015 % of reading/°C max low level voltage
|
|
common mode rejection |
> – 120 dB 50/60 Hz
|
|
isolation between channels and bus |
1780 V AC for 60 s
2500 V DC for 60 s |
|
isolation between channels |
220 V AC
300 V DC |
|
update time |
1000 ms
|
|
fault type |
Broken wire
Overtacking scale |
|
marking |
CE
|
|
cold junction compensation |
Internal 32…140 °F (0…60 °C)
|
|
local signalling |
1 LED green bus communication is present (Active)
1 LED red external fault 8 LEDs green channel is turned on 8 LEDs red channel fault |
|
bus current requirement |
280 mA
|
|
power dissipation in W |
1.5 W
|
|
module format |
Standard
|
|
product weight |
0.66 lb(US) (0.3 kg)
|
standards |
CSA C22.2 No 142
UL 508 |
|
---|---|---|
product certifications |
CUL
FM Class 1 Division 2 |
|
resistance to electrostatic discharge |
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2 |
|
resistance to electromagnetic fields |
9.14 V/yd (10 V/m) 80…1000 MHz conforming to IEC 801-3
|
|
ambient air temperature for operation |
32…140 °F (0…60 °C)
|
|
ambient air temperature for storage |
-40…185 °F (-40…85 °C)
|
|
relative humidity |
95 % without condensation
|
|
operating altitude |
<= 16404.2 ft (5000 m)
|