Description
range of product | Modicon STB distributed I/O solution |
---|---|
product or component type | Standard analog input kit |
kit composition | STBACI8320 module STBXBA2000 base STBXTS1100, 6-terminal screw type connector STBXTS2100, 6-terminal spring clamp connector |
analogue input type | Current 0…20 mA Current 4…20 mA |
analogue input number | 4 |
communication port protocol | Hart protocol tolerance |
analogue input resolution | 15 bits + sign |
type of filter | Single low pass input filter 985 Hz |
absolute maximum input | 25 mA/50 V DC |
---|---|
cold swapping | Yes |
hot swapping fallback | Yes for standard NIMs |
fallback status | State 0 basic NIMs User configurable standard NIMs |
data format | EN 61131-2 IEC 61131-2 |
update time | 80 ms |
integral linearity | +/- 0.05 %FS |
input impedance | 250 Ohm |
maximum supply current for sensors | 25 mA per input channels |
protection type | Short-circuit protection |
absolute accuracy error | +/- 0.4 % of full scale 25 °C |
temperature drift | +/-0.005 %/°C |
insulation between channels and logic bus | 1780 V for 1 minute |
insulation between channels and sensor bus | 200 V |
addressing requirement | 8 input words |
product compatibility | Power distribution module STBPDT3100/3105 Mounting base STBXBA2000 |
[Us] rated supply voltage | 24 V DC |
supply | Power distribution module |
current consumption | 95 mA at 5 V DC for logic bus |
marking | CE |
overvoltage category | II |
status LED | 1 LED (green) module status (RDY) 1 LED (red) module error (ERR) |
depth | 70 mm |
height | 18.4 mm |
width | 128.3 mm |
product certifications | CSA C-Tick ATEX Cat 3G FM Class 1 Division 2 UL |
---|---|
pollution degree | 2 conforming to IEC 60664-1 |
operating altitude | <= 2000 m |
IP degree of protection | IP20 conforming to EN 61131-2 class 1 |
ambient air temperature for operation | -25…70 °C |
ambient air temperature for operation | 32…140 °F without derating |
ambient air temperature for storage | -40…85 °C without derating |
ambient air temperature for storage | -40…185 °F without derating |
relative humidity | 95 % at 60 °C without condensation |
vibration resistance | +/-0.35 mm at 10…58 Hz 3 gn at 58…150 Hz on 35 x 7.5 mm symmetrical DIN rail 5 gn at 58…150 Hz on 35 x 15 mm symmetrical DIN rail |
shock resistance | 30 gn for 11 ms conforming to IEC 88 reference 2-27 |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Weight | 146.0 g |
Package 1 Height | 3 cm |
Package 1 width | 8 cm |
Package 1 Length | 13 cm |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 28 |
Package 2 Weight | 4.599 kg |
Package 2 Height | 15 cm |
Package 2 width | 30 cm |
Package 2 Length | 40 cm |
Unit Type of Package 3 | PAL |
Number of Units in Package 3 | 448 |
Package 3 Weight | 65.408 kg |
Package 3 Height | 60 cm |
Package 3 width | 80 cm |
Package 3 Length | 448 cm |