Description
range | PowerLogic |
---|---|
product name | PowerLogic PM5000 |
device short name | PM5111 |
product or component type | Power meter |
power quality analysis | Up to the 15th harmonic |
---|---|
device application | Power monitoring |
type of measurement | Current Voltage Frequency Power factor Energy Active and reactive power |
supply voltage | 100…415 V AC 45…65 Hz 125…250 V DC |
network frequency | 50 Hz 60 Hz |
[In] rated current | 5 A 1 A |
type of network | 3P 1P + N 3P + N |
maximum power consumption in VA | 10 VA at 415 V |
ride-through time | 80 ms 120 V AC typical 100 ms 230 V AC typical 100 ms 415 V AC typical |
display type | Backlit LCD |
display resolution | 128 x 128 pixels |
sampling rate | 64 samples/cycle |
measurement current | 10…9000 mA |
analogue input type | Voltage (impedance 5 MOhm) Current (impedance 0.3 mOhm) |
measurement voltage | 35…690 V AC 45…65 Hz between phases 20…400 V AC 45…65 Hz between phase and neutral |
frequency measurement range | 45…65 Hz |
number of inputs | 0 |
measurement accuracy | Active energy +/- 0.5 % Reactive energy +/- 2 % Active power +/- 0.5 % Apparent power +/- 0.5 % Frequency +/- 0.05 % Power factor +/- 0.005 Current +/- 0.5 % Voltage +/- 0.5 % |
accuracy class | Class 0.5S active energy conforming to IEC 62053-22 |
number of outputs | 1 digital |
communication port protocol | Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none – 2 wires, insulation 2500 V JBUS |
communication port support | RS485 |
data recording | Time stamping Min/max of instantaneous values |
connections – terminals | Voltage circuit: screw terminal block4 Control circuit: screw terminal block2 Current transformer: screw terminal block6 Input/output circuit: screw terminal block6 RS485 link: screw terminal block4 |
mounting mode | Flush-mounted |
mounting support | Framework |
standards | IEC 61557-12 EN 50470-1 UL 61010-1 IEC 62053-24 IEC 60529 EN 50470-3 IEC 62053-22 |
product certifications | CE conforming to IEC 61010-1 CULus conforming to UL 61010-1 MID conforming to EN 50470-1 MID conforming to EN 50470-3 |
width | 96 mm |
depth | 72 mm |
height | 96 mm |
net weight | 380 g |
electromagnetic compatibility | Limits for harmonic current emissions class A conforming to IEC 61000-3-2 Electrostatic discharge level 4 conforming to IEC 61000-4-2 Conducted RF disturbances level 3 conforming to IEC 61000-4-6 Magnetic field at power frequency level 4 conforming to IEC 61000-4-8 Conducted and radiated emissions class B conforming to EN 55022 |
---|---|
IP degree of protection | IP52 front: conforming to IEC 60529 IP30 body: conforming to IEC 60529 |
relative humidity | 5…95 % at 50 °C |
pollution degree | 2 |
ambient air temperature for operation | -25…70 °C |
ambient air temperature for storage | -40…85 °C |
operating altitude | 2000 m |
Unit Type of Package 1 | PCE |
---|---|
Package 1 Length | 13.0 cm |
Number of Units in Package 1 | 1 |
Package 3 Width | 80.0 cm |
Package 3 Weight | 61.82 kg |
Package 2 Width | 30.0 cm |
Package 2 Height | 30.0 cm |
Package 2 Weight | 6.64 kg |
Number of Units in Package 3 | 96 |
Unit Type of Package 3 | P06 |
Package 3 Height | 80.0 cm |
Package 3 Length | 60.0 cm |
Package 1 Width | 12.5 cm |
Package 1 Height | 11.5 cm |
Package 1 Weight | 550.0 g |
Number of Units in Package 2 | 12 |
Unit Type of Package 2 | S03 |
Package 2 Length | 40.0 cm |