Description
range of product | PowerLogic PM700 |
---|---|
device short name | PM750 |
product or component type | Power meter |
power quality analysis | Total harmonic distortion |
---|---|
type of measurement | Current Voltage Frequency Power factor total Apparent power total Active power total Reactive power total Apparent power per phase Active power per phase Reactive power per phase Energy |
supply voltage | 125…250 V DC 115…415 V AC 45…65 Hz |
network frequency | 45…65 Hz |
maximum power consumption in VA | 5 VA |
display type | Backlit LCD |
display resolution | 6 lines |
sampling rate | 32 samples/cycle |
measurement current | 5 A 1 A |
input type | Current 0.005…6 A (impedance <= 0.1 Ohm) |
measurement voltage | 10…480 V AC 45…65 Hz phase to phase 10…277 V AC 45…65 Hz phase to neutral |
number of inputs | 2 digital |
measurement accuracy | Frequency 0.02 Hz 45…65 Hz Power factor 0.0034 1A to 6A and from -0.5 to +0.5 Current 0.4 % 1…6 A Voltage 0.3 % 50…227 V Power 0.5 % |
accuracy class | Class 2 reactive energy conforming to IEC 62053-23 Class 0.5S active energy conforming to IEC 62053-22 Class 0.5 active energy conforming to ANSI C12.20 |
number of outputs | 1 digital (static) |
communication port protocol | Modbus 19.2 kbauds |
communication port support | RS485 |
data recording | Alarms Min/max of instantaneous values |
electromagnetic compatibility | Limits for harmonic current emissions: , conforming to IEC 61000-3-2 Conducted and radiated emissions: , conforming to EN 55011 class B Electrostatic discharge immunity test: , class III, conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields: , class III, conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test: , class III, conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test: , class III, conforming to IEC 61000-4-5 Conducted RF disturbances: , class III, conforming to IEC 61000-4-6 Immunity to impulse waves: , class III, conforming to IEC 61000-4-8 Immunity to microbreaks and voltage drops: , class III, conforming to IEC 61000-4-11 Limitation of voltage changes, voltage fluctuations and flicker in low-voltage: , conforming to IEC 61000-3-3 |
---|---|
mounting mode | Flush-mounted |
mounting support | Panel |
type of installation | Indoor installation |
overvoltage category | III |
IP degree of protection | IP30 back: conforming to IEC 60529 IP52 front face: conforming to IEC 60529 |
relative humidity | 95 % at 50 °C |
pollution degree | 2 |
ambient air temperature for operation | -5…50 °C |
ambient air temperature for storage | -40…85 °C |
operating altitude | 0…3000 m |
standards | IEC 61010-1 CSA C22.2 No 14 UL 508 |
product certifications | CE cULus |
width | 96 mm |
depth | 69 mm |
height | 96 mm |
net weight | 0.37 kg |