Description
Range of Product | Altistart 48 |
---|---|
Product or Component Type | Soft starter |
product destination | Asynchronous motors |
Product Specific Application | Heavy duty industry and pumps |
device short name | ATS48 |
utilisation category | AC-53A |
Ue power supply voltage | 208…690 V – 15…10 % |
power supply frequency | 50…60 Hz – 5…5 % |
motor power kW | 110 kW 660 V for standard applications 110 kW 690 V for standard applications 30 kW 230 V for severe applications 37 kW 230 V for standard applications 55 kW 400 V for severe applications 55 kW 440 V for severe applications 75 kW 400 V for standard applications 75 kW 440 V for standard applications 75 kW 500 V for severe applications 75 kW 525 V for severe applications 90 kW 500 V for standard applications 90 kW 525 V for standard applications 90 kW 660 V for severe applications 90 kW 690 V for severe applications |
Maximum Horse Power Rating | 100 hp 460 V for standard applications 100 hp 575 V for severe applications 125 hp 575 V for standard applications 30 hp 208 V for severe applications 40 hp 208 V for standard applications 40 hp 230 V for severe applications 50 hp 230 V for standard applications 75 hp 460 V for severe applications |
device connection | In the motor supply line |
---|---|
protection type | Phase failure line Thermal protection motor Thermal protection starter |
standards | EN/IEC 60947-4-2 |
Product Certifications | UL C-tick CSA TCF CCC NOM 117 DNV GOST SEPRO |
marking | CE |
discrete input number | 5 |
discrete input type | PTC, 750 Ohm 77 °F (25 °C) Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm |
discrete input logic | Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA |
minimum switching current | 10 mA 6 V DC relay outputs |
discrete output number | 2 |
discrete output type | LO1) logic output 0 V common configurable LO2) logic output 0 V common configurable R1) relay outputs fault relay NO R2) relay outputs end of starting relay NO R3) relay outputs motor powered NO |
analogue output type | Current output AO 0-20 mA or 4-20 mA 500 Ohm |
communication port protocol | Modbus |
Connector Type | 1 RJ45 |
communication data link | Serial |
physical interface | RS485 multidrop |
Transmission Rate | 4800, 9600 or 19200 bps |
Function Available | External bypass (optional) |
operating position | Vertical +/- 10 degree |
Height | 13.39 in (340 mm) |
Width | 7.87 in (200 mm) |
Depth | 10.43 in (265 mm) |
Net Weight | 27.34 lb(US) (12.4 kg) |
electromagnetic compatibility | Conducted and radiated emissions level A IEC 60947-4-2 Conducted and radiated emissions level B IEC 60947-4-2 Damped oscillating waves level 3 IEC 61000-4-12 Electrostatic discharge level 3 IEC 61000-4-2 Immunity to electrical transients level 4 IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 Voltage/current impulse level 3 IEC 61000-4-5 |
---|---|
relative humidity | 0…95 % without condensation or dripping water EN/IEC 60068-2-3 |
ambient air temperature for operation | 104…140 °F (40…60 °C) with current derating of 2 % per °C) 14…104 °F (-10…40 °C) without derating) |
Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
operating altitude | <= 3280.84 ft (1000 m) without derating > 3280.84…6561.68 ft (> 1000…2000 m) with current derating of 2.2 % per additional 100 m |
Category | 22579-OPEN ATS48 ALTISTART |
---|---|
Discount Schedule | CP1G |
GTIN | 3389110982367 |
Returnability | Yes |
Country of origin | ID |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 13.39 in (34 cm) |
Package 1 Width | 16.93 in (43 cm) |
Package 1 Length | 18.11 in (46 cm) |
Package 1 Weight | 32.83 lb(US) (14.892 kg) |
Unit Type of Package 2 | P06 |
Number of Units in Package 2 | 2 |
Package 2 Height | 28.94 in (73.5 cm) |
Package 2 Width | 31.50 in (80 cm) |
Package 2 Length | 23.62 in (60 cm) |
Package 2 Weight | 85.98 lb(US) (39 kg) |